Pressure Intrument Failures in Chemical Plants:8 Common Issues, Diagnosis & Proven Solutions

In high-risk environments like chemical plants, pressure instrument are critical for monitoring operational safety and efficiency. However, challenges such as pressure insrument failures, inaccurate readings, and mechanical damage can lead to costly shutdowns or safety hazards. This comprehensive guide addresses the most common pressure measurement issues in industrial settings, including vibration-induced gauge damagecapillary tube breakage, and negative pressure fluctuations. Backed by real-world case studies and technical analysis, we provide actionable solutions to optimize your pressure control systems, reduce downtime, and comply with safety standards.
1280X1280

1. Pressure Interlock Fault

1280X1280 1

Fault Phenomenon:

In a heavy oil main pipeline pressure alarm interlock system of a petrochemical company, the pressure of the heavy oil main pipeline for boiler fuel decreased, and the standby pump failed to start automatically. This caused the heavy oil pressure to continue dropping until the boiler interlock activated, cutting off the heavy oil supply and resulting in a shutdown.
 

Fault Analysis:

  • Normally, when the heavy oil main pipeline pressure drops to a certain value, the standby pump should start automatically to maintain a certain flow rate and pressure of heavy oil. The failure of the standby pump to start indicates that it did not receive the signal of pressure drop, meaning that the pressure transmitter in this system did not detect the change in main pipeline pressure.

  • The investigation revealed that the isolation fluid inside the impulse line was drained, allowing heavy oil to enter the impulse line and the positive chamber of the transmitter. Since isolation fluid was used to measure the main pipeline pressure, and no heat tracing was applied to the impulse line and instrument, the heavy oil, which has a relatively low solidification point, solidified inside the impulse line and diaphragm chamber, preventing it from sensing and transmitting changes in main pipeline pressure. Additionally, due to the expansion of solidified heavy oil, the sensor element indicated an excessively high force and maintained this value.

  • When the main pipeline pressure dropped, this value remained unchanged, causing the standby pump not to start, ultimately leading to a shutdown incident.

Handling Method:

Use steam to blow through the impulse line, disassemble and clean the diaphragm chamber with gasoline. Before re-commissioning the instrument, perform a static pressure test to ensure it is qualified, then refill the impulse line with isolation fluid.

2. Pressure Indicator Returning to Zero

1280X1280 3
Fault Phenomenon:
 
In a pyrolysis gasoline pressure detection system of a petrochemical company, shortly after the insulation heating was turned off, the pressure indicator returned to zero, the control valve closed completely, and the cracking tower stopped discharging material. This resulted in a shutdown incident due to excessively high tower level.
 
Fault Analysis:
 
  • Due to significant pressure fluctuations during normal operation, the system used a method of opening up the primary pressure tap valve and controlling resistance with a needle valve to reduce the fluctuation of the instrument’s indication. However, because the instrumentation technician did not fully understand the specifics of this system, they reduced the primary pressure tap valve size when the instrument indication fluctuated too much. Given the large diameter of the primary pressure tap valve, it was difficult to control precisely. Once the primary pressure tap valve was closed down to a point where the pressure indication fluctuation was within an acceptable range.

  • the valve was essentially fully closed. This issue was not noticed during regular operations. After turning off the insulation heating, the impulse line cooled down, causing the originally vaporized medium inside to condense into liquid, reducing in volume and causing a sudden drop in pressure (almost to zero). If the pressure tap valve was not fully closed, the condensed liquid from the tower would refill the impulse line, maintaining pressure consistency between the instrument and the tower.

  • With the valve fully closed, it became a sealed container. During insulation, the medium was in a vaporized state with higher or stable pressure. When the temperature dropped, the medium liquefied, causing the pressure to decrease and the indication to return to zero. The zero signal from the instrument caused the control valve to close completely, leading to a rapid increase in tower level and resulting in a shutdown incident.

Handling Method:

Open the primary pressure tap valve to restore normal indication. It should be noted that for some high-pressure detection control systems, throttling resistance is often used to reduce detection fluctuations, but the resistance must be controlled appropriately; otherwise, the aforementioned faults may occur, leading to severe consequences.

3. Inaccurate Pressure Measurement

微信图片 20250222211943

Fault Phenomenon:

The measured pressure is p = 6.5 MPa, using a bourdon tube pressure gauge for pressure detection. The environmental temperature where the instrument is located is +40°C, and the process requires accuracy to within 1%, with an accuracy class of 0.5. The selected instrument has a range of 0 to 20 MPa. Process operators reported that the gauge was inaccurate.
 

Fault Analysis:

During on-site valve closure pressure testing, the instrument operated well but did not accurately indicate the process pressure. After removing the pressure gauge and sending it to the calibration lab, its readings still met the specified standards. According to the selection principles for measuring instruments, the measured value should be around 2/3 of the upper limit of the measurement range. Therefore, the ideal upper limit of the range is:
 
Ideal range upper limit = 6.5 × 2/3 = 9.75 MPa
Thus, the instrument’s range should be 0 to 10 MPa.
Referring to tables, the temperature coefficient of bourdon tube pressure gauges is approximately 0.0001 to 0.001. If we take the temperature coefficient as 0.0001 and the ambient temperature changes from 20°C to 40°C, the additional error caused by temperature change is: ΔP = 6.5 × 0.0001 × (40 – 20) = 0.013 MPa
Thus, the allowable absolute error of the instrument is: = 0.065 – 0.013 = 0.052 MPa
The selected range of the instrument is too large, leading to inaccurate measurements.
 

Handling Method:

Select an instrument range of 0 to 10 MPa with an accuracy of 0.5 class. By replacing the existing gauge with one having a range of 0 to 10 MPa while maintaining the original 0.5 class accuracy, the fault of inaccurate pressure measurement can be resolved.

4. Capillary Tube Breakage in Single Flange Pressure Measurement Instruments

微信图片 20250222212153

Fault Phenomenon:

A facility using a single flange for pressure measurement experienced a capillary tube breakage, resulting in a system shutdown.

Fault Analysis:

The reasons for the capillary tube breakage include the following aspects:
  • Mechanical damage: The single flange capillary pressure measurement instrument consists of a flange, capillary tube, and transmitter. Any mishandling during transportation, calibration, or installation can cause damage to the capillary tube. Additionally, activities around the instrument during its use can also lead to accidental damage.

  • Vibration damage: If the instrument is installed in a part of the high-pressure circuit that experiences significant vibration, the capillary tube may fatigue and break over time due to continuous vibration.

  • Material issues: If the measured medium is corrosive or prone to crystallization, improper material selection for the capillary tube can lead to problems such as: firstly, if the single flange diaphragm is damaged, the measuring medium can quickly enter the capillary tube, causing internal corrosion and breakage; secondly, the presence of corrosive substances like ammonia in the measuring environment can also cause external corrosion and breakage of the capillary tube.

  • Quality issues: Inappropriate welding materials or poor welding between the capillary tube, transmitter, and flange can also result in capillary tube breakage.

  • Improper selection of filling silicone oil: Insufficient filling of silicone oil can lead to diaphragm puncture, causing the capillary tube to break.
 

Handling Method:

Since each instrument has a service life and lifespan, it is important to replace new transmitters periodically for critical instruments in special environments. Manufacturers should use specialized materials for key components of instruments used in specific applications to achieve optimal performance. Special care must be taken during transportation, calibration, and installation to ensure instrument safety. Regular inspections and maintenance of the instruments should also be conducted.

5. Large Fluctuations in Furnace Negative Pressure During Heavy Wind and Rain

微信图片 20250222213055 1

Fault Phenomenon:

The furnace negative pressure of a plant fluctuates significantly under conditions of high winds and heavy rain.
 

Fault Analysis:

Furnace negative pressure is a strictly controlled process parameter in production processes, which should not fluctuate significantly. The reasons for significant fluctuations in negative pressure under conditions of high winds and heavy rain are as follows.

  • Rainwater infiltration on the negative pressure side during rainy days.
  • As the furnace negative pressure is very low (around -80Pa), differential pressure transmitters are generally used to measure it. Strong winds alter the force acting on the transmitter, especially under irregular wind speeds, causing significant fluctuations in the transmitter’s input signal. This results in fluctuation of the regulator output and the actuator, creating a vicious cycle of negative feedback that leads to significant fluctuations in the instrument indication.
 

Handling Methods:

  • Modify the installation method of the transmitter by adding a short pressure guiding pipe to the atmospheric end on the negative pressure side, pointing downwards, or redirect the outlet of the transmitter’s negative chamber to a sheltered area to prevent rainwater from forming static pressure and avoid the impact of strong winds on the instrument.
  • Adding an air capacitor to the output line of the transmitter can also help reduce indication fluctuations.

6.Indication of the negative pressure in the cracking furnace chamber is lower than expected.

微信图片 20250222214451

Fault Phenomenon:

The pressure transmitter indicates a low signal.
 

Fault Analysis:

A water collection tank is used for measuring the negative pressure in a cracking furnace to prevent condensate from moist air entering the negative pressure transmitter, which would increase measurement errors. As shown in Figure 9.1, moisture in the humid air continuously condenses into water. When the water level in the pressure guiding pipe’s water collection tank rises above the height of the inlet on the right side of the pipe, i.e., when the water level in the water collection tank exceeds a certain point, due to the influence of the furnace negative pressure, it causes a column of water. The height of this water column is denoted as H, and the additional pressure generated by the liquid column (r being the relative density of water) acts on the pressure (vacuum) transmitter. This additional pressure exerts a force opposite to that of the furnace negative pressure, leading to a lower indication of negative pressure.
output

Where p is the indicated pressure of the differential pressure transmitter.

微信图片 20250222215241
Due to the existence of Hr, the indicated pressure is lower.
 

Handling Methods:

Regularly drain the accumulated water, especially during shutdown periods when humid air enters the pipe and accumulates more water. Therefore, before restarting the furnace, it is best to discharge the accumulated water. Another solution is to modify the piping arrangement, changing the pressure guiding pipe of the furnace chamber to the configuration shown by the dashed line, which can also reduce the frequency of draining.

7.Pressure Measurement Indication Fluctuations

微信图片 20250222215729

Fault Phenomenon:

In a natural gas pressure regulation system, fluctuations occurred in the subsequent process sections. Switching the regulator to manual control eliminated the fluctuations in the subsequent sections, but the fluctuation in the pressure regulator’s measurement indication remained, albeit less pronounced.
 

Fault Analysis:

Upon inspecting the pressure transmitter and opening the drain valve, it was observed that the pressure quickly dissipated with some residual gas, indicating that the primary pressure tap valve was blocked. Due to this blockage and the long pressure guiding pipe, changes in pipeline pressure took a long time to reach the transmitter’s sensing element, causing lagged and cumulative pressure transmission. This inevitably led to continuous variations in the transmitter output. When the regulator was switched to automatic control, adjustments based on these false signals caused fluctuations in the system medium pressure, exacerbating the fluctuation phenomenon.
 

Handling Methods:

After removing the pressure guiding pipe, it was found that the valve was severely clogged with carbon deposits. Clearing the primary pressure tap valve with a wire and restarting the system restored normal operation of the gauge.

8.Bypass Shut-off Valve Leakage Causes Low Indication

Fault Phenomenon:

Pressure indication is lower than expected.
 

Fault Analysis:

Inspection showed that the pressure transmitter was functioning normally and the control valve was fully closed, indicating that the regulation system was operating correctly. However, upon touching the bypass line, it was found to be very hot, suggesting significant leakage from the process bypass shut-off valve.
 

Handling Methods:

The process operators were notified, and after repairing the bypass shut-off valve, pressure control returned to normal.Fault diagnosis of the pressure system was conducted.

9.Explanation Using a Steam Pressure Regulation System as an Example:

微信图片 20250222220302
  • The steam pipeline pressure recording suddenly drops to zero, and the safety valve trips. When a fault occurs between meters causing sudden changes in the control valve’s opening degree, it results in a sharp increase in steam pressure, but the recording instrument does not respond. In such cases, switch to manual remote control of the control valve before addressing the fault.

  • If the steam pipeline pressure recorded value does not exceed the setpoint yet the safety valve trips, instrumentation personnel should compare relevant instruments. If all points’ temperatures are normal, it indicates that the safety valve is improperly adjusted. If the temperature values at various points are high, it suggests that the pressure recording value is lower than the actual pressure.

  • For large but slow pressure fluctuations, the cause should generally be sought from the process side.

  • For rapid oscillatory pressure fluctuations, investigate parameter tuning and issues intrinsic to the instruments themselves.

  • Variations in load, reflux, temperature, and improper operation can all lead to changes in internal equipment pressure. It is necessary to look for causes from the perspective of process operation.

  • One should be aware of the usual pressure fluctuation patterns of each instrument, distinguishing between abnormal and normal conditions, and use other process parameters as references for judgment.

Safe Replacement and Installation of a Pressure Gauge

output 1

 

Work Process:

  • Prepare tools and equipment — Record pressure data — Close the root valve of the pressure gauge — Open the pressure relief valve to completely release pressure — Dismantle the old pressure gauge — Clean out deformed old gaskets and debris — Install the new pressure gauge (with gasket) — Close the pressure relief valve — Slowly open the root valve of the pressure gauge — Leak test — Confirm and record the pressure values, serial numbers of the old and new pressure gauges — Clean up the site and recover tools and equipment.

Wear appropriate personal protective equipment (PPE) as required to prevent clothing from getting entangled and to avoid static electricity in flammable and explosive environments.
 

Tools and Equipment Preparation:

Adjustable wrench or open-end wrench, pressure gauge, pressure gauge fitting, screwdriver, Teflon tape, fine sandpaper, several gaskets suitable for the working pressure within 1/3 to 2/3 of the gauge range, one bottle of soapy water (for leak testing).
output 2

Pressure Gauge Inspection:

  • Ensure the seal is intact.
  • Verify that it is within the valid inspection period.
  • Check if the pointer returns to zero.
  • Gently tap to ensure there’s no displacement.
  • Ensure all screws are tightened.
  • Check that dust holes and ventilation holes are unobstructed and that screws are undamaged.
  • Confirm that the accuracy class meets requirements.
  • Ensure the dial has no cracks and the scales are clear.
微信图片 20250222221030

Dismantling the Pressure Gauge:

  • Slowly close the shut-off valve of the pressure gauge and wait until the pointer returns to zero before dismantling. Use an adjustable wrench to hold the gauge fitting and an open-end wrench to remove the pressure gauge without damaging it.
  • After loosening the pressure gauge, support it with your hand while gently swaying it side-to-side to release any remaining pressure.
  • Place the removed pressure gauge in a dry, dust-free location for inspection by relevant departments.
  • Use cotton cloth and a screwdriver to clean debris inside the gauge fitting, check if the threads are intact, and ensure the pressure tapping hole is not blocked. If the fitting is normal, tighten it without replacement.
  • Record pressure data, close the root valve of the pressure gauge, slowly open the pressure relief valve, and once pressure is fully released, use an adjustable wrench to secure the root valve and an open-end wrench to remove the pressure gauge.
  • Support the loosened pressure gauge with your hand, gently sway it side-to-side to release any remaining pressure.
  • Place the removed pressure gauge on a large cloth (or in a pressure gauge box).
  • Use cotton cloth and a hook needle to clean debris inside the gauge cock, check if the threads are intact, and ensure the pressure tapping hole is unobstructed.
微信图片 20250222221302

 

Risk Warning:

Choose a reasonable standing position, stand sideways to avoid injury from valve leakage.
Close the control valve of the old pressure gauge to cut off the pressure source.
When removing the gauge, do not hold the top of the pressure gauge to prevent injury from residual pressure forcing the gauge out.
微信图片 20250222221712
  • Use an adjustable wrench and a fixed wrench to dismantle the old pressure gauge in the correct direction. When the pressure gauge becomes very loose from the fitting, hold the gauge with one hand while gently twisting and slightly shaking it to release any remaining pressure inside the gauge.
微信图片 20250222221302
Risk Warning: Do not place your head close to the pipeline outlet to prevent injury from residual pressure.
  • Clear any sealing tape and debris from inside the pressure gauge fitting to prevent blockage of the gauge’s pressure inlet.
微信图片 20250222222045
Risk Warning: Do not insert your bare hand into the threads. Use appropriate tools (such as a screwdriver or awl) for cleaning.
Installation of the Pressure Gauge:
  • Wrap the qualified pressure gauge’s threads with PTFE tape (Teflon tape) in a counterclockwise direction to avoid blocking the pressure inlet. Pay special attention not to cover the inlet hole with the tape.
  • Wind the PTFE tape around the threads in a clockwise direction for 3-5 turns.
  • Hold the pressure gauge steady on the fitting with your hand, and initially tighten it by hand for several turns to ensure correct alignment. Then, use a wrench to fully tighten the gauge.
  • Ensure that the orientation of the pressure gauge is parallel to the pipeline for easy observation.
output 3
  • Hold the pressure gauge steady and align it properly, then mount the gauge onto the fitting. Turn it by hand for several threads to ensure it is correctly aligned. Use both a fixed wrench and an adjustable wrench to securely tighten the pressure gauge.
 
Key Points: Ensure the pressure gauge is perpendicular to the pipeline and oriented for easy observation.
微信图片 20250222222540
Risk Warning:Do not apply excessive force when tightening to avoid overpressure that could damage the gauge. Ensure the test pressure does not exceed 0.05 MPa to prevent damage to the gauge’s needle.
Pressure Testing and Leak Checking:
  • Close the pressure gauge cock’s pressure relief valve, then slowly open the root valve to allow pressure to rise gradually. This prevents sudden pressure surges that could damage the gauge pointer.
  • Once the working pressure is reached, ensure it falls within the 1/3 to 2/3 range of the pressure gauge’s capacity. The system should neither leak nor seep at this pressure level to be considered qualified.
  • Record the pressure values along with the serial numbers of the new and old pressure gauges. Clean up the site and recover all tools and equipment used.
Inclusion:
Effective pressure instrument management in chemical production requires a proactive approach to troubleshooting industrial pressure systems and addressing root causes like improper calibrationenvironmental stress, or material incompatibility. By selecting vibration-resistant gauges for high-impact zones, ensuring proper installation with accessories like siphon tubes, and conducting regular maintenance (e.g., draining condensate or clearing clogged impulse lines), facilities can mitigate risks of pressure interlock faults or measurement inaccuracies. For specialized applications—such as hydrogen pipelines or steam systems—always prioritize industry-specific gauges and validate their performance under extreme conditions. Invest in training personnel to recognize early warning signs, such as erratic pointer movements or silicone oil discoloration, to prevent catastrophic failures and maintain operational integrity.
未命名图片 2
Please enable JavaScript in your browser to complete this form.